TYPICAL FLOOR PLAN
Full-floor @ 12,570 +/- rentable square feet Half-floor @ 6,285 +/- rentable square feet
Removal of center demising wall creates one full-floor lab & office suite
LABORATORY BUILDING SYSTEMS
-
ELECTRICAL SERVICE
208/120V power provided to electrical closets on each floor, conduit runs from electrical closet to panel in Tenant suite. Lab electric capacity = 7.5 watts per usable SF of lab area.
-
BACK-UP POWER CAPACITY
2.5 watts per useable SF of lab area; connected to 350 kW/480v diesel emergency generator.
-
PLUMBING
Tempered water for emergency shower and eye wash station. Building managed pH-neutralizing system.
-
HVAC
Labs designed with central air handling HVAC system providing 100% non-circulated air at 1.25 cfm per usable lab SF (8 ACH). Humidity designed for no more than 60% RH. N+1 redundancy for exhaust fan, pumping, and boilers.
-
CEILING HEIGHTS / FLOOR LOAD
Deck-to-deck: 11’-6” / Deck-to-grid: 8’-6”
Floor load suitable for typical lab use. -
BUILDING ELEVATORS
One (1) 3,500 lb. capacity freight elevator, 250 f.p.m. (entry door: 3’-4”/ cab size: 4’-10” x 6’-8” x 7’-11”). Two (2) 2,500 lb. capacity passenger elevators, 250 f.p.m.
-
Developed & Managed by:
Based in New Haven, Connecticut, The Hurley Group is a real estate development and management firm with over one million+ square feet of office, retail, industrial, warehouse, flex/creative space and apartments.
Learn more at www.hurleygroup.net.
-
Designed by:
Svigals + Partners, LLP is a full-service architecture firm and a leading authority on laboratory/bioscience master planning, design and construction/FFE services founded in 1983 and located in New Haven, Connecticut.